产品阐述 |
input 0/4 ma ... 20 ma 2 x output 0/4 ma ... 20 ma |
一般特性 |
signal type |
analog input |
供电 |
连接器 |
power rail or terminals 14 , 15- |
额定电压 |
20 ... 35 v dc |
纹波 |
在电源容限内 |
功耗 |
1.8 w |
功耗 |
2.4 w |
输入 |
连接器 |
terminals 1 , 2-, 3 or 5-, 6 |
输入信号 |
0/4 ... 20 ma |
开路电压/短路电流 |
terminals 1 , 3-: 22.7 v / 38 ma |
电压降 |
terminals 5, 6 : ≤ 2.4 v at 20 ma |
输入电阻 |
terminals 2-, 3: max. 76 ω terminals 1 , 3: max. 500 ω (250 ω load) |
available voltage |
terminals 1 , 3: ≥ 16 v at 20 ma |
输出 |
连接器 |
terminals 7-, 8 ,9; 10-, 11 ,12 |
负载 |
0 ... 550 ω |
输出信号 |
0/4 ... 20 ma (overload > 25 ma) |
纹波 |
max. 50 μa rms |
transfer characteristics |
偏差 |
at 20 °c (68 °f), 0/4 ... 20 ma ≤ 10 μa incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
频率范围 |
field side into the control side: bandwidth with 0.5 vpp signal 0 ... 7.5 khz (-3 db) control side into the field side: bandwidth with 0.5 vpp signal 0.3 ... 7.5 khz (-3 db) |
settling time |
200 μs |
指令符合 |
电磁兼容性 |
|
|
directive 2004/108/ec |
en 61326-1:2006 |
conformity |
电磁兼容性 |
ne 21:2011 |
防护等级 |
iec 60529:2001 |
周围环境 |
环境温度 |
-20 ... 60 °c (-4 ... 140 °f) |
机械特性 |
防护等级 |
ip20 |
重量 |
approx. 200 g |
外形尺寸 |
20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in) , housing type b2 |
安装 |
on 35 mm din mounting rail acc. to en 60715:2001 |
data for application in connection with ex-areas |
ec-类型 鉴定证书 |
bas 99 atex 7060 , for additional certificates see www.pepperl-fuchs.com |
|
保护型号、类别、组别 |
ii (1)gd, [ex ia] iic, [ex iad], (-20 °c ≤ tamb ≤ 60 °c) [circuit(s) in zone 0/1/2] |
ec-类型 鉴定证书 |
dmt 01 atex e 133 |
|
保护型号、类别、组别 |
i (m1) [ex ia] i |
符合标准 |
tüv 99 atex 1499 x , observe statement of conformity |
|
group, category, type of protection, temperature class |
ii 3g ex na ii t4 [device in zone 2] |
指令符合 |
|
|
94/9/ec 指令 |
en 60079-0:2012 , en 60079-11:2007 , en 60079-15:2010 , en 61241-11:2006 , en 50303:2000 |
international approvals |
ul认证 |
|
|
控制图 |
116-0173 (culus) |
iecex approval |
iecex bas 04.0016 |
|
approved for,, |
[zone 0] [ex ia] iic, [ex iad], [ex ia] i |
一般说明 |
注释 |
both output loads must be connected to ensure complete and correct operation within the technical specification. |